Permit: T05PL00436

Parcel: 119042200


Addresses:

3649 S LIBERTY AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/22/2005 PLUMBING - FINAL Approved IVRS - Inspection :* 1) ALL CORRECTIONS HAVE BEEN MADE
03/16/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* 1) VENT FROM WATER HEATER TO BE EXTENDED MINIMUM 2' ABOVE TOP OF ROOF LINE WITH DOUBLE WALL VENT PIPING. 2) PROVIDE BONDING OF BUILDING GAS PIPING
03/09/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL REMOVE THE UNION IN LINE AND REPLACE WITH A RIGHT & LEFT HAND NIPPLE. 2) GAS LINE SHALL BE LOCATED A MINIMUN OF 6" ABOVE GROUND. 3) SHALL SEAL ALL GAS LINE. LINE PENETRATIONS THRU WALLS. ( EXTERIORS) 4) SHALL STRAP DOWN GAS SUPPLY DROP TO WATER HEATER. 5) SHALL EXTEND T & P DRAIN FOR WATER HTR TO DAYLIGHT AND TERMINATE 6" ABOVE GROUND AND CAP OFF 1 1/2" DRAIN.