Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/04/2005 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :*CORRECTION MADE |
| 03/03/2005 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 03/02/2005 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* 1) CONNECT INTERIOR PIPING TO YARD PIPING AND TEST ENTIRE GAS SYSTEM MINIMUN 10 PSI WITH NO PRESSURE DROP FOR 15 MINUTES. 2) WHERE UNIONS ARE NECESSARY LOFT-RIGHT NIPPLES & COUPLINGS SHALL BE USED. 3) SECURE ALL GAS PIPING CORRECTLY. 4) PROVIDE BONDING OF BUILDING GAS SYSTEM. 5) VENT FROM FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE DOUBLE WALL TO TERMINATION WITH APPROVED CAP 2' ABOVE COOLER INTAKE. |