Permit: T05PL00386

Parcel: 135060270

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/08/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03/04/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* PROVDE APPROVED PRIMER & TAPE ON ALL UNDERGROUND FITTINGS & WRENCH MARKS. PROVIDE A SHUT OFF VALVE PRECEDING UNION FOR BLDG. SH??OFF. RETEST SYSTEM. PROVIDE A BOND JUMPER ON NEW GAS PIPE. PROVIDE APPROVED SHUT OFF VALVES AT APPLIANCES. REMOVE COPPER FLEX FROM T & P DRAIN & USE SOLID PIPE 3/4" I. D. PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF VENT CONNECTORS. SEAL PENETRATION IN WALL. RECALL FOR INSPECTION.