Permit: T05PL00319

Parcel: 11709213E


Addresses:

205 E 22ND ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/24/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
02/23/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) GAS PRESSURE TEST SHALL BE MIN. 10 LBS. WITH REQUIRED TEST GAGE 1/10 INCREMENTS. 2) SHALL EXTEND T & P DRAIN TO DAYLIGHT OR APPROVED RECEPTOR. FOR WATER HTR. 3) SHALL REMOVE ALL UNIONS IN LINE AND REPLACE WITH RIGHT & LEFT HAND NIPPLES. 4) MAX. LOCATION OF SHUT OFF VALVE FOR WATER HEATER IS 3" -0" OF DEVELOPED LENGHT.