Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05PL00294
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/07/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
03/03/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SEE 301.1.194 UPC MINIMUN STDS. PLUMBERS TAPE HAS NO LISTING FOR BEING AN APPROVED HANGER. 2) SEE TABLE 3-1 PIPE SUPPORTS. 3) UNABLE TO LOCATE PLANS OR PERMITS FOR ALL THE NEW PLUMBING BEING INSTALLED UNDER THE FLOOR. 4) PRESSURE TEST OK. 5) NEED TO SEE HOW HEATER VENT IS CONNECTED TO CHIMNEY-AND ITS TERMINATED POINT 504.1, 520.0 522.0 | |
02/28/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) GAS PIPING MAY NOT PASS UNDER THE BLDG. THIS IS NOT EXISTING-NEW PIPE HAS BEEN RUN. | |
02/22/2005 | PLUMBING - FINAL | Cancelled | GAS PRESSURE TEST NOT READY PER GREG CLARK OF 661-1316 | |
02/22/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* NOT READY |