Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT LOCATE A THREADED FITTING IN A CONCEALED LOCATION FOR BLDG. SEWER FOR WEST BLDG. DRAIN AND PROVIDE A PERM GLUED CAP 2) OK TO BACKFILL TRENCH AND RELEASE WATER TEST. LEAVE PERM CAP OPEN FOR REINSPECTION 3) SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT AT WATER HEATER VENT CONNECTOR AND AT APPLIANCE COLLAR 4) SHALL EXTEND T & P DRAIN AND TERMINATE 1" ABOVE WATER HTR DRIP PAN 5) SHALL PROVIDE A PRESSURE RELIEF VALVE ? JET AT 125 PSI AT EXTERIOR C.W. SUPPLY |