Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK. 2) ALL CORRECTIONS HAVE BEEN MADE. | |
| 02/15/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PRESSURE TEST SHALL BE MIN 10 LBS 2) CANNOT HAVE A FLEX CONNECTOR PENETRATE THE APPLIANCE HOUSING @ WALL FURNACE. 3) WATER HTR T & P VALVE IS NOT WORKING. 4) WATER HTR DBL WALL FLU VENT REQUIRES 1" CLEARANCE AROUND COMBUSTIONABLE MATERIAL. 5) SHALL PROVIDE A LO?? AIR VENT MIN 10 X 10 LOCATED 12" ABOVE WATER HTR FLOOR BASE. |