Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/28/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 3/8" ID X 24" GAS FLEX CONNECTOR ONLY ADEQUATE UP TO 85,000 BTU. READ THE MANUFACTURERS LISTING ON THE FLEX |
|
| 02/14/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 15 PSI TEST IS OK. 3/8" I.D GAS FLEX CONNECTOR TO FURNACE NOT ADEQUATE FOR 100, 000 BUT. SECURE GAS LINE TO WALL. RECALL FOR INSPECTION. |