Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05PL00232

Parcel: 129050740


Addresses:

2624 E EASTLAND ST

Inspection Status: Denied

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/16/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* COMPLETE ALL WORK THEN CALL FOR INSPECTION
02/15/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) READ ALL NOTES FROM 2/8/05 INSPECTION AND COMPLY. 2) THREAD PROTECTORS ARE NOT APPROVED COUPLINGS. 3) PROVIDE APPROVED CAP ON DOUBLE WALL WATER HEATER VENT 2' ABOVE TOP OF ROOF
02/08/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*1) GAS PIPING TO BE MINIMUM 6" ABOVE FINISH GRADE. 2) PROVIDE PERMIT FOR 2622 E-EAST LAND FOR NEW GAS PIPING. 3) WATER HEATER VENTS TO BE CONNECTED PROPERLY DOULBE WALL VENT PIPING TO HAVE MINIMUN 1" CLEARANCE FROM COMBUSTABLES. 4) VENTS FROM GAS BURNING APPLIANCES WHEN WITHIN 10' OF COOLER INTAKE TO BE MINIMUM 3' ABOVE TOP OF COOLER INTAKE. 5) WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN TO BE PIPED DOWN WARD TO 6"-24" FROM FINISH GRADE. 6) PROVIDE BONDING OF BUILDING GAS PIPING. 7) SECURE PIPING AT 8' INTERVALS ( NO ACCESS TO 2622 E EASTLAND RED TAGGED GAS METER THIS MAY NOT BE A COMPLETE LIST)