Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2005 | PLUMBING - GAS PRESSURE TEST | Approved | ||
| 02/23/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/17/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL REMOVE UNION IN LINE ON ROOF AND PROVIDE RIGHT & LEFT HAND NIPPLE 2) SHALL SUPPORT AND STRAP DOWN EXISTING GAS SUPPLY ON ROOF TO GAS PACK EVERY 6'. 3) SHALL EXTEND WATER HTR FLU VENT AND TERMINATE 3' ABOVE CO??. 4) SHALL EXTEND WATER HTR T & P DRAIN TO DAYLIGHT. 5) SHALL PROVIDE AGA OR CSA GAS SHUT OFF VALVE @ WATER HTR. 6) SHALL PROVIDE PROPER SIZE VENT CONNECTOR AND FLU VENT FOR WATER HTR. 2) MAX LENGHT OF FLEX CONNECTOR FOR STEAM TABLE IS 3' 0'' 8) RE TEST THE SYSTEM. |