Permit: T05PL00146

Parcel: 126172080


Addresses:

4040 E 17TH ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05PL00146

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/16/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
02/11/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) NEED CORRECT PRESSURE RELIEF DEVICE INSTALLED YOU HAVE INSTALLED A PRESSURE REGULATING VALVE.
02/07/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* PETITION OF APPEAL # 2005.152 ONSITE. 1) INSTALL THE 125 # PRESSURE RELIEF VALVE AT EXTERIOR H20 SUPPLY PIPING. 2) PROVIDE PERMIT FOR NEW WALL HEATER OR HAVE ADDED TO THIS PERMIT. 3) VENT FROM WALL HEATER TO BE 2' ABOVE TOP OF COOLER WHEN WITHIN 10' OF COOLER INTAKE. 4) SECURE PIPING TO NEW WALL HEATER. 13 PSI AIR TEST FROM METER TO NEW BUILDING SERVICE VALVE TO WATER HEATER STOVE AND WALL HEATER OK
02/02/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* 1) PROVIDE RIDGID PIPING THRU WALL WITH AGA OR CSA APPROVED SHUT OFF VALVE OUTSIDE OF HEARTH WITHIN 4' OF HEARTH WITH 10 PSI MINIMUN TEST. 2) PROVIDE VENT FOR FIREPLACE AND LISTING FOR ARTIFICIAL LOG INSIDE FIREPLACE. 3) PROVIDE BONDING OF BUILDING GAS PIPING SYSTEM. 4) WATER HEATER TEMPERATURE & PRESSURE RELIEF TO GRAVITY DRAIN TO DAYLIGHT OR PROVIDE CITY SIGNED PETITION OF APPEAL ON SITE WITH APPROVED INSTALLATION OF WATER HEATER TEMPERATURES & PRESSURE PIPING & VALVES