Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05PL00144
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 02/16/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE A WATER HTR ENCLOSURE FOR WATER HTRS LOCATED @ A EXTERIOR LOCATION. 2) SHALL EXTEND & TERMINATE T & P DRAIN 6" ABOVE FLOOR. 3) SHALL REMOVE ASBESTOS WATER HTR FLU VENT AND PROVIDE SINGLE WALL FLU VENT AND CAP TERMINATE 3" ABOVE COOLER. 4) SHALL EXTEND FURNACE FLU VENT 2' ABOVE COOLER. 5) SHALL PROVIDE ROOF FLASHING FOR ALL GAS PENETRATIONS THRU ROOF. 6) SHALL REMOVE ALL UNIONS IN LINE AND REPLACE WITH RIGHT & LEFT HAND NIPPLES. 7) SHALL STRAP & SUPPORT GAS LINE ON ROOF ?? 6' WALL FURNACE HOUSING. 9) SHALL PROVIDE AGA OR CSA GAS SHUT OFF VALVES FOR ALL APPLIANCES. 10) GAS LINE HAS BEEN PAINTED PRIOR TO INSPECTION I CANNOT VERIFY MARKINGS ON PIPE. 11) RE TEST THE SYSTEM. |