Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK. 2) ALL CORRECTIONS HAVE BEEN MADE | |
| 02/07/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE A APPROVED ROOF FLASHING FOR ALL PENETRATIONS THRU ROOF SEE SECTION 313.8 94 UPC. 2) SHALL PROVIDE # 6 BONDING WIRE TO GROUND GAS SYSTEM TO ELECTRIC PANEL OR TO GROUNDED H20. 3) RETEST THE SYSTEM. 4) OK TO BACKFILL TRENCH. |
|
| 01/28/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL CHECK GAS SYSTEM WITH SOAPY WATER. GAGE IS @ 6LBS. A 10 LBS OF TEST REQUIRED. 2) SHALL PROVIDE A 10 X 10 MIN LOUVER GRILLLOCATED 12" ABOVE WATER HTR BASE ON ENCLOSURE DOOR. 3) CANNOT LOCATE A GAS APPLIANCE IN THE BEDROOM . SHALL RELOCATE FLOOR HTR TO ANOTHER LOCATION. AND REMOVE GAS LINE SUPPLY TO THIS HTR. |