Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/06/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHERE UNIONS ARE NECESSARY LEFT-RIGHT NIPPLES AND COUPLINGS SHALL BE USED 2) THREAD PROTECTORS ARE NOT APPROVED COUPLINGS 3) PIPING IN CEILING SPACE REQUIRES HANGERS AT XORRECT INTERVALS 4) VENT FROM REGULATOR AT BOILER TO BE RAN TO DAYLIGHT |
|
| 04/04/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/02/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE CITY APPROVED GAS ISOMETRIC DRAWING. 2) PROVIDE LISTING PLATES WITH BTU REQUIREMENTS FOR ALL APPLIANCES. 3) WHERE ??ARE NECESSARY LEFT RIGHT NIPPLES & COUPLINGS SHALL BE USED. 4) PROVIDE ROOF TOP ACCESS FOR INSPECTION OF GAS PIPING. 5) PROVIDE BONDING OF BUILDING GAS SYSTEM. 6) PROVIDE CORRECT VENTING OF GAS APPLIANCES |
|
| 01/19/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |