Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/03/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*ALL LIGHTING IN SHOP AREAS TO BE 12" AFF SEAL ALL HOLES IN PANELS, GREEN WIRES IN PANELS TO BE TAPED WHITE. INSTALL RECEPTACLE COVERS ON ONES MISSING OUTDOOR BAY AREA _ WEATHERPROOF COVER MISSING AND ONE SWITCH COVER NOT WEATHER PROOF OUTSIDE PANEL MISSING DEAD FRONT COVER OUTSIDE CONDUIT WITH FEEDERS FOR LIFT MACHINE NORTH SIDE- CONDUIT TO BE SUPPORTED & WIRING BOXED |