Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEW BOX NEEDS TO HAVE PLASTIC BUSHING BEHIND DISCONNECT CORRECTLY INSTALLED. 2. STRAP GROUND WIRE 3. ADDRESS NEW DISCONNECT |
|
| 02/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAIN DISCONNECT NEEDS TO BE REPLACED: FUSE HOLDER BROKEN AWAY FROM STAND, TERMINATION OF WIRE HAZARDOUS-ADDRESS SERVICE 2) STRAP GROUND WIRE TO STRUCTURE 3) ADD 2 SCREWS TO BOTTOM OF SUB-PANEL TO HOLD COVER DOWN 4) INSTALL COVER SLOTS ON MISSING BREAKER SLOTS 5) REQUIRED WORK BY OWNER AND NEEDS TO BE DONE BY LICENSED ELECTRICAL CONTRACTOR |