Permit: T05OT03034

Parcel: 11004345J


Addresses:

3305 N SWAN RD #105

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
03/19/2006 SIGN ELECTRIC Approved IVRS - Inspection :*
OK SIGN
03/16/2006 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*
STEVE TO RESCHEDULE
02/27/2006 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*
1. PROTECT GTO CABLE FROM SHARP METAL EDGES OF FLEX
2. SWITCH TO BE CAPABLE OF BEING LOCKED OUT 600.6
3. A MARKING LABEL IS NEEDED
4. FILL UNUSED OPENINGS IN BACK OF LETTERS & STRIP
5. MAINTAIN GTO CLEARANCE TO GROUNDED SURFACES ALSO DO NOT CROSS GTO CABLES
6. TRANSFORMERS & SPLICES TO BE ENCLOSED AWAY FROM COMBUSTIBLES.
7. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR
02/24/2006 SIGN ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SIGN CONTRACTOR CANNOT MEET TODAY TO RESCHEDULE FOR MONDAY
02/22/2006 SIGN ELECTRIC Cancelled CANCELLED PER MICHELLE OF EFFECTIVE SIGNS #323-0665
02/22/2006 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*