Inspection Status: Partial Approval
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2006 | SIGN ELECTRIC | Partial Approval | IVRS - Inspection :*INSTALL MARKING LABEL 600.4 SWITCH TO BE CAPABLE OF BEING LOCKED OUT 600.6 PLEASE PROVIDE AN ACCESS TO SPACE WITH POWER SUPPLY AND SECURE WALKWAY TO DECK. 600.21 |
|
| 01/06/2006 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* |