Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
Permit Number - T05OT02982
Inspection Description - PLUMBING - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
03/31/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
03/30/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EACH WATER SUPPLIED FIXTURE OR APPLIANCE REQUIRES ITS OWN BACKFLOW DEVICE. MAY NOT COMBINE SUPPLIES EACH MUST HAVE ITS OWN DRAIN SODA FOUNTAIN HAS THREE WATER SUPPLIED DEVICES. 1. CARBONATOR 2. DRINKING WATER 3. ICE MAKER 2. HOSE BIBBS REQUIRE VACUUM BREAKERS 3. WYE STRAINER AT CAR WASH UPSIDE DOWN 4. PROVIDE LISTING FOR CO2 STORAGE VESSEL PIPED IN COPPER. |
|
03/23/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ALL WATER SUPPLIED APPLIANCES REQUIRE BACKFLOW PROTECTION: INCLUDING HOSE BIBBS, WATER AIR STATION, CARWASH, AND EACH WATER SUPPLIED APPLIANCE INSIDE INCLUDING RODA FOUNTAINS, ICE MAKERS, AND BINS ETC. EACH DRAIN TO BE SEPARATE AND IF EXCEEDS FIVE FEET TO BE DIRECTLY TRAPPED PIPING TO BE INSTALLED AND SUPPORTED TO 2003 UPC. WILL NEED TO SEE COPIES OF BACKFLOW CERTIFICATION ALL INDIRECT WASTE PIPING TO HAVE A MINIMUM OF 1" AIR GAP. ADA INSPECTION BY BLDG. INSP. ALL SINKS REQUIRED CLEANOUTS. WILL REQUIRE YOUR BLUE PRINTS TO MATCH YOUR FLOOR PLAN, OR REVISE PLAN TO MATCH INSTALLATION. |