Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*RECEPTACLES WITHIN 18" OF FLOOR TO BE EXPLOSION PROOF AND SEALED OFF RECEPTACLES TO BE GFCI PROTECTED CLEAN EXCESS PAINT FROM DEVICE TERMINALS FIXTURES TO USE APPROVED WIRING METHODS UNGROUNDED CONDUCTOR NOT TO BE WHITE SECURE BOXES AND CONDUITS TO WALL ELECTRICAL LISTED CONDUITS AND FITTINGS NEEDED NM CABLES NOT FOR USE IN THIS OCCUPANCY INSTALL SERVICE PER CODE REQUIREME?? AND UTILITY SPEC'S ALSO INTERIOR PANELS FILL UNUSED OPENINGS IN BOXES AN ELECTRICAL PLAN WILL BE NEEDED FOR WORK TO BE INSTALLED ALSO ADD 2035 TO PERMIT |