Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2006 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 03/03/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1. CANNOT USE 600 V TERMINATIONS ON 15000V WIRE. 2. MAINTAIN HIGH VOLTAGE TO GROUND SPACING. 3. A MARKING LABEL IS NEEDED 4. WE HAVE NO POWER AT THIS TIME 5. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. 6. CONDUCTOR COLORING TO BE FOR 277 V (BROWN, ORANGE, YELLOW) |
|
| 03/01/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELLED: NEED TO RESCHEDULE FOR EARLY MORNING ACCESS ON SITE |