Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2006 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
| 03/29/2006 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* WILL RESCHEDULE |
|
| 03/21/2006 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* 1. MARKING LABELS ARE NEEDED 600.4 2. TIGHTEN LOOSE FITTINGS 3. SECURE TRANSFORMER ENCLOSURE 4. SUPPORT MC CABLE & FLEX OVER 4' |