Permit: T05OT02339

Parcel: 13316037K

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/09/2006 PLUMBING - FINAL Approved PLUMBING FINAL IS OK
OK FOR C OF O
12/28/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHALL PROVIDE A ELONGATED WATER CLOSET WITH OPEN FRONT SEAT
2) SHALL PROVIDE A CLEANOUT AT SINK. CLEANOUT MAYBE LOCATED ON TRAP ARM PROVIDING THAT THE CLEANOUT IS VERTICAL ABOVE THE FLOW LINE