Permit: T05OT02317

Parcel: 127070550


Addresses:

5101 E 8TH ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
01/06/2006 BUILDING - FINAL Approved IVRS - Inspection :*APPROVED PER CORRCTION AND APPEAL TO BUILDING OFFICIAL
11/16/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ANSI 117.1 ACCESSIBILITY GUIDE
2) SIDEWALK TO BE ACCESSIBLE (RAMP FROM SIDEWALK)
3) LEVER HANDLE, NO KNOWLEDGE HARDWARE REQUIRED AT ACCESSIBLE ENTRIES, BATHROOM, BEDROOM AND COMMON AREAS
3) THRESHOLD TO BE NO MORE THAN 1/2" HIGH WITH NO MORE THAN 1/4" VERTICAL RISE
4) HALLWAY FOR SIDE ACCESS TO ACCESSIBLE SPACE (BED AND BATH) MUST BE 42" WIDE MINIMUM
5) CLEAR FLOOR SPACE REQUIRED AT ACCESSIBLE LAVATORY
6) RIM OF LAV TO BE NO HIGHER THAN 34"
7) LEVER HANDLES REQUIRED AT LAV, ACCESSIBLE TOILET AND ACCESSIBLE BATH REQUIRED
8) REPAIR TPRV DISCHARGE LINE
9) REAR EXIT REQUIRED TO BE SIDE HINGED
10) BACKFLOW PREVENTERS REQUIRED ON HOSE BIBS
11/14/2005 BUILDING - FINAL Cancelled
11/14/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*