Permit: T05OT02288

Parcel: 11205283F

Inspection Status: Not ready for Inspection

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
10/11/2005 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*SUPPORT M/C CABLE WITHIN 12'' OF BOXES & TRANSFORMER
SWITCH TO BE AS PER 600.6
A MARKING LABEL AS PER 600.4 IS NEEDED
MAINTAIN GTO CLEARANCES 1 1/2" FROM GROUNDED SURFACES
TIGHTEN LOOSE FITTINGS