Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T05OT02176
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2007 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
09/25/2007 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. JUNCTION BOX OVERFILLED 314.16 2. GROUND JUNCTION BOX 250.148 3. SUPPORT M/C CABLE AS PER 330.30 |
|
02/28/2006 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. A LICENSED ELECTRICAL CONTRACTOR TO PERFORM WORK ON POWER CIRCUIT. STOP WORK UNTIL A CONTRACTOR IS OBTAINED. |