Inspection History Details
Permit: T05OT02175
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2005 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 12/09/2005 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* "THE HOME DEPOT" 1. TIGHTEN LOOSE FITTINGS 2. JUNCTION BOX WHERE SPLICES ARE MADE NEED TO BE GROUNDED "CONTRACTOR PICK UP" "TOOL RENTAL CENTER" 1. SWITCH TO BE CAPABLE OF BEING LOCKED OUT 2. PLEASE BOND TRANSFORMER/DRIVER ENCLOSURE 3. A MARKING LABEL IS NEEDED FOR SIGN 600.4 "NURSERY" 1. A LOCK OUT FOR SWITCH 600.6 2. CHECK FITTINGS FOR TIGHTNESS 3. A MARKING LABEL IS NEEDED 600.4 PLEASE REVISE PLANS FOR DELETED SIGN OR INSTALL |