Permit: T05OT01903

Parcel: 134113750

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05OT01903

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2007 MECHANICAL - FINAL Approved PER INSP CARD
05/15/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
KITCHEN HOOD MEETS TYPE 1 REQUIREMENTS AS PER UMC
GREASE DUCTS DO NOT MEET CODE. MUST USE MIN. 16 GA. WELDED DUCT. IF USING AN UPBLAST FAN, BE SURE FANS TERMINATE ABOVE EVAP. COOLER. IF DUCT IS NOT INSIDE A RATED SHAFT, USE FIRE WRAP ON DUCT.
02/22/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
08/10/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) KITCHEN HOOD EQUIPMENT AND GREASE DUCT NOT TYPE I. 2) EXHAUST FAN NOT INTERLOCKED WITH MAKE UP AIR
3) COOKING APPLIANCES NOT FITTING UNDER HOOD
4) EXHAUST FAN APPEARS TO BE TYPE I BUT DUCT IS NOT