Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2007 | MECHANICAL - FINAL | Approved | PER INSP CARD | |
| 05/15/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* KITCHEN HOOD MEETS TYPE 1 REQUIREMENTS AS PER UMC GREASE DUCTS DO NOT MEET CODE. MUST USE MIN. 16 GA. WELDED DUCT. IF USING AN UPBLAST FAN, BE SURE FANS TERMINATE ABOVE EVAP. COOLER. IF DUCT IS NOT INSIDE A RATED SHAFT, USE FIRE WRAP ON DUCT. |
|
| 02/22/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/10/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN HOOD EQUIPMENT AND GREASE DUCT NOT TYPE I. 2) EXHAUST FAN NOT INTERLOCKED WITH MAKE UP AIR 3) COOKING APPLIANCES NOT FITTING UNDER HOOD 4) EXHAUST FAN APPEARS TO BE TYPE I BUT DUCT IS NOT |