Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T05OT01823
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2005 | SIGN SHOP | Approved | IVRS - Inspection :* 1) OK SIGN |
|
08/29/2005 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) WORK IS PROGRESSING 2) NO JUNCTION BOX-SUPPORT M/C CABLE AS PER CODE |
|
08/24/2005 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) MAINTAIN SPACKLING TO HIGH VOLTAGE TERMINALS 1 1/2" 2) MAINTAIN GTO TO GROUNDED SURFACES 1 1/2" 3) BOND REAR WAY 600.7 4) ISO LATE PRIMARY POWER TO SWITCH 5) FILL IN USED OPENINGS IN RACEWAY 6) PLEASE VERIFY JUNCTION BOX ACCESS |
|
08/22/2005 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE RESCHEDULE |
|
08/10/2005 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) SIGN CONTRACTOR TO PROVIDE ACCESS TO INSPECT SIGN 2) A MARKING LABEL IS NEEDED 600.4 |
|
08/05/2005 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) NO SIGN INSTALLED-NO PHONE NUMBER, NO ADDRESS OF SHOP 2) ELECTRIC CORDS NOT ALLOWED ABOVE CEILING |