Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :*CORRECTIONS MADE OK OK FOR C OF O PENDING ANY OTHER INSPECTION |
|
| 10/23/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*SEE NOTE NUMBER 2 FROM 090805 INDIRECT WASTE PIPING FROM FOUNTAIN IS NOT APPROVED SINGLE WALL VENT CONNECTOR MAY NOT PASS THRU CEILING. INSTALL 3 SCREWS AT EACH VENT CONNECTOR FITTING ICE MACHINE WILL NOT BE RECONNECTED/ |
|
| 10/21/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/11/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*SEE NOTE # 2 FROM 090805 PROVIDE BOND BETWEEN GAS AND WATER PIPING CONNECT FLUE PIPING CORRECTLY |
|
| 09/08/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) WATER HEATER INSTALLED WITHOUT BENEFIT OF INSPECTION. WILL REQUIRE: PROPERLY CONNECTED VENT SYSTEM, GRAVITY T & P RELIEF DRAIN, DIELECTRIC PROTECTION AGAINST DISSIMILAR METALS, BOND BETWEEN WATER AND GAS PIPING AND EXPANSION TANK 2) REMOVE ALL INDIRECT WASTE PIPING FROM SODA DISPENSOR NOT BEING USED 3) DISCONNECT ICE MACHINE IF YOU ARE NOT USING IT |
|
| 08/28/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ADDRESS POSTED 2) MULTIPLE CODE VIOLATIONS INCLUDING BUT NO LIMITED TO INDIRECT WASTE PIPING, CARBONATOR, NO CLEANOUT AT SINK AND NO EXPANSION TANK 3) HAVE A PLUMBER TAKE A LOOK-MAKE CORRECTIONS AND RECALL INSPECTION |