Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05OT01736

Parcel: 13506136C


Addresses:

2544 S KOLB RD


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05OT01736

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/03/2005 BUILDING - FINAL Approved IVRS - Inspection :*
1) ALL CORRECTIONS MADE PER CODE
2) OK FOR FINAL C OF O
08/01/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PERMIT REQUIRED FOR NEW ELECTRIC BRANCH CIRCUITS
2) 1" AIR GAP REQUIRED ABOVE FLOOD RIM OF FLOOR SINK FOR INDIRECT WASTE
3) RPG BACKFLOW DEVICE MUST BE PROPERLY MOUNTED. PLUMBERS TAPE IS NOT A SUITABLE MOUNTING DEVICE
4) FIX LEAK AT RPG UNDER SINK
5) PROVIDE BACKFOW PROTECTION FOR WATER AT SODA MACHINE AND FOR ICE TEA MAKER
6) PROVIDE SUPPORT FOR ABS MAXIMUM 4' ON CENTER. CORRECT BACKFLOW PROTECTION AT KITCHEN SODA MACHINE AND 1" AIR GAP AT FLOOR DRAIN UNDER ICE MAKER
07/20/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) BACKFLOW PROTECTION HAS BEEN REMOVED FROM ICE MACHINE AND SODA DISPENSORS. TESTABLE BACKFLOW DEVICES ARE REQUIRED FOR WATER SUPPLY TO ALL CARBONATORS (SODA DISPENSORS), WATER DISPENSORS AND ANY ICE MACHINE THAT DOES NOT HAVE AN INTEGRAL (1" AIR GAP) BACKFLOW PREVENTOR
2) CAP UNUSED GAS LINE BY KITCHEN ENTRANCE
3) REMOVE THROW BOLT AT REAR EXIT
4) YOU MUST BE READY TO OPEN THAT MEANS ALL FIXTURES IN PLACE
07/19/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
07/18/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH INSTALLING ALL FIXTURES AND HAVE BUSINESS IN "TURN-KEY" READINESS
2) SODA BAR AND 3 COMPARTMENT SINK AND LAVATORY ON NORTH WALL AT MIDDLE OF STORE WERE INSTALLED WITHOUT PERMITS. REMOVE THEM OR GET A PERMIT AND INSPECTIONS FOR THEM
3) ALL EQUIPMENT IN STORE (FRYERS, ICE MACHINES, ETC...) MUST BE SET-UP. TO INSTALL A NEW STIR FRY STATION REQUIRES A PERMIT AND INSPECTION
4) PLANS/PERMITS AND INSPECTION CARD MUST BE ON SITE