Date Description Inspector Results Comments
08/16/2005 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
1) SEPERATE 277V AND 120V IN BOX WITH SWITCH DEVICE
2) TRANSFORMER TO HAVE GROUNDING SYSTEM TO BLDG STEEL
3) INSTALL MARKING LABELS 600.4
4) MAINTAIN GTO CLEARANCES FROM GROUNDED PARTS AND OTHER GTO CABLES
5) NEED PLANS FOR LED LIGHTING