Permit: T05OT01585

Parcel: 11520005P

Inspection Status: Approved

Inspection History: CERTIFICATE OF OCCUPANCY

Permit Number - T05OT01585

Inspection Description - CERTIFICATE OF OCCUPANCY

Inspection Status - Approved

Date Description Inspector Results Comments
07/06/2005 CERTIFICATE OF OCCUPANCY Approved IVRS - Inspection :*
07/01/2005 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL DOORS EXCEPT PRIVATE OFFICE (HAS 2 DOORS) REQUIRE LEVER HANDLE "NO KNOWLEDGE" HARDWARE PER CHAPTER 11 OF IBC AND CHAPTER 10 IBC "NO KNOWLEDGE" MEANS THEY COME UNLOCKED FROM EGRESS SIDE WITH NO PINCHING, TWISTING OR TIGHT GRASPING
2) ADA SIGN AT RESTROOM BELONGS ON WALL AS INDICATED NOT DOOR
3) HOT WATER LINE AT LAV SHOULD BE INSULATED
4) FLUSH HANDLE ON TOILET TO BE ON OPEN SIDE
2)
06/30/2005 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) FROM DOOR REQ'S EXIT SIGN. 2) INSTALL " THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS " SIGN AT MAIN DOOR". 3) INSTALL GRAB BARS IN H.C RESTROOM. 4) INSTALL LEVER HANDLE ON H.C RESTROOM DOOR. 5) INSTALL ADA SIGN AT HC RESTROOM ADJACENT TO DOOR.
06/29/2005 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
There is no access to the site.| 920* DOOR LOCKED NO ACCESS