Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05OT01539

Parcel: 126020010


Addresses:

4668 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
03/20/2006 SIGN SHOP Approved IVRS - Inspection :*
12/19/2005 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
11/12/2005 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
1. TIGHTEN ALL LOOSE FITTING TO MAINTAIN BENDING PATH
2. MAINTAIN GTO CLEARANCES
3. SWITCH TO BE CAPABLE OF BEING LOCKED OUT FOR LED 600.6
4. ACCESS HOLE TOO SMALL 600.21
5. SUPPORT M/C CABLE 6' & 42" FROM BOXES
6. FINISH ITEMS #2&4 PREVIOUS INSPECTION
7. SIGN NOT TO BE ENERGIZED UNTIL FINALED BY ELECTRICAL INSPECTOR
08/12/2005 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PLEASE RE-SCHEDULE
07/19/2005 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
1) CONDUIT FITTINGS TO TERMINATIONS
2) MAINTAIN GTO CLEARANCES 1 1/2"
3) SUPPORT M/C CABLES INDISE FLOURESCENT CABINETS
4) NEED MARKING LABELS 600.4