Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2005 | SIGN SHOP | Approved | IVRS - Inspection :* 1) OK SIGNS |
|
| 09/08/2005 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) MARK TO RESCHEDULE |
|
| 08/10/2005 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) INSTALL LOCK NUTS CORRECTLY AND TIGHTEN 2) SHEET METAL SCREW NOT ALLOWED FOR BONDING 250.8 3) MAINTAIN 1 1/2" GT0 CLEARANCES 4) M/C CABLE TO TERMINATE INTO A FITTING |