Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: SIGN SHOP
Permit Number - T05OT01108
Inspection Description - SIGN SHOP
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2005 | SIGN SHOP | Not ready for Inspection | 1) BOND RACEWAY 600.7 2) UNTANGLE GTO AND MAINTAIN SEPARATION. 3) SUPPORT FLEX OVER 4' 4) MAKING LABEL AS PER 600.4IVRS - Inspection :* |