Inspection History Details
Inspection Status: Partial Approval
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2005 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1) BOND RACEWAY 600.7 2) MAINTAIN 1 1/2" CLEARANCE FOR GTO CABLE TO GROUNDED SURFACES. 3) REPLACE BROKEN BOOT SPLICES. |