Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 04/21/2005 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection :* |
| 04/19/2005 |
SIGN ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection :* 1) BOND LETTERS PER 600.7. 2) ACCESS TO BE PROVIDED AS PER 600.21. 3) OPEN UP LETTER FOR VERIFICATION OF LED'S TO USAGE IN S.A.M. ALSO TRANSFORMERS/DRIVERS. 4) SWITCHING TO BE AS PER 600.6 5) LOW VOLTAGE CONTROL CABLE TO BE PLENEUM RATED. PLEASE PROVIDE ALL PAPERWORK. |