Permit: T05OT00678

Parcel: 12209003A


Addresses:

3919 E PIMA ST

Inspection Status: Not ready for Inspection

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
04/13/2005 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*1) ISOLATE PRIMARY POWE TO SWICH IN SIGN. 2) BOND RACEWAY. 3) A JUNCTION BOX IS NEEDED- WE HAVE EXPOSED CONDUCTORS AND OPEN SPLICES. 4) A MARKING LABEL IS NEEDED. 5) PLEASE HAVE PLANS AND PERMITS ON SITE. 6) USE APPROVED CONNECTORS AND WIRING METHODS. 7) SUPPORT GTO CABLE 1 1/2" -SPAGATTI GLASS IS NOT AN INSULATOR. 8) MISISNG RACE WAY COVERS. 9) PROPERLY TERMINATE HIGH VOLTAGE CONNEC