Permit: T05OT00625

Parcel: 133243720

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
04/04/2005 SIGN ELECTRIC Approved IVRS - Inspection :*
04/01/2005 SIGN ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*1) SIGN WIRING TO BE # 10 AWG MIN IF USED. UL 20.1.4 OR USE LISTED GTO CABLE-CONDUCTOR TO BE INSULATED. 2) CONDUCTOR NOT TO BE SPLICED WITH PRODUCTS LISTED AT VOLTAGE LESS THAN APPLIED. 3) CONDUCTOR TO BE PROTECTED PER UL 19.3.1 TO TERMINAL. 4) BOND RACEWAY 600.7. 5) PRIMARY CONDUCTORS TO BE ISOLATED TO SWITC-CITY SIGN REQUIREMENTS.