Permit: T05OT00544

Parcel: 129043210


Addresses:

421 S NORRIS AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/08/2005 PLUMBING - FINAL Approved IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVE OK. 3) THIS INSPECTION IS FOR GAS PACK ON ROOF ONLY
07/06/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) GAS PRESSURE TEST IS BELOW 10 LBS MIN. CHECK THE SYSTEM. 2) SHALL PROVIDE TWO HOLE STRAPS AND SECURE GAS DROP FROM ROOF TO WALL P TAPE IS NOT APPROVED MATERIAL.
06/13/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* 1) TO RECEIVE GAS AT THIS LOCATION A 10 PSI MININUM TEST SHALL BE ON PLACE ON SYSTEM WITH NO DROP FOR 15 MINUTES. 2) PROVIDE BONDING OF BUILDING GAS PIPING. 3) SECURE & SUPPORT GAS PIPING AT DROP TO METER & ON ROOF. 4) ALL GAS VALVES TO BE AGA OR CSA APPROVED.