Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05OT00313
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/25/2005 | PLUMBING - FINAL | Approved | ||
03/23/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE A BACKFLOW PREVENTER 007 FOR ICE MAKER. 2) SHALL HAVE ALL IN HOUSE BACKFLOW PREVENTERS TESTED & CERTIFIED BY TIME OF FINAL INSPECTION. 3) SHALL PROVIDE A P-TRAP FOR HAND SINK@ BAR INDERECT WASTE AND @ DBL COMPT. SINK. 4) SHALL PROVIDE AN EXPANSION TANK @ WATER HTR. 5) SHALL REPLACE T & P VALVE AND REMOVE FLEX LINE IN T & P DRAIN. 6) SHALL PROVIDE A 1/2" MIN INDEPENDENT DRAIN FOR 009 BACKFLOW PREVENTER FOR SODA DISPENSER |
|
03/21/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DOOR IS LOCKED |
|
03/16/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ALL EQUIPMENT TO BE INSTALLED AND MEET MINIMUM REQUIREMENTS FOR 94 UPC. 2) PLEASE HAVE CITY APPROVED PLAN SHOWING ALL PLUMBING EQUIPMENT. |