Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/23/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 02/18/2005 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* 1) NEW METAL 4 PLEX OUTLETS BOXES TO BE GROUNDED. 2) PLEASE VERIFY LOADS & CIRCUITS FOR NEW EQUIPMENT 3) SUPPORT CONDUITS ABOVE PANEL. 4) A GROUND BAR IS NEEDED- WE HAVE MULTIPLE CONDUCTORS UNDER A TERMINAL LUG |