Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05OT00050
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/04/2005 | BUILDING - FINAL | Approved | APPEAL APPROVED AND SIGNED BY JESSIE SANDERS | |
06/10/2005 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) EGRESS, LIGHTING, ETC OK-BUT INTERNATIONAL CODES ASK FOR TYPE 1 HOOD, CHURCH ONLY HAS SMALL ELECTRIC RANGE WITH TYPE 2 HOOD. FOR C OF O THE CHURCH WILL NEED TO APPEAL REQUIREMENT OF TYPE 1 HOOD. SEE DAVID MANN AT 201 N. STONE |
|
05/24/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIX: 12" ADDRESS DISPLAY REQUIRED ON BLDG AND HOSE BIB REQUIRES ANTI-SIPHON DEVICE (BY ELECTRIC METER) 2) EXISTING BLDG IS ONLY SEMI-ACCESSIBLE EG-A) RESTROOMS HAVE ACCESSIBLE W.C. AND TURNING RADIUS BUT NO ADA COMPLIANT LAVATORY B) ACCESSIBLE ROUTE IS NOT COMPLIANT WITH MODERN CODE (1:12 CURB RAMP AND MAXIMUM THRESHOLD) C) NOT ALL HARDWARE MEETS ACCESSIBLE (CHAPTER 11) REQUIREMENTS BUT SANCTUARY AND RESTROOMS DO-PER CHAPTER 34 OF IBC. NO CHANGE REQUIRED FOR 3 ABOVE |