Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) WATER HEATER VENT INSTALLED UPSIDE DOWN 2) DO NOT CUT DBL WALL PIPE 3) WILL LEAVE GAS CARD ON FINAL |
|
| 01/06/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE 2) LEFT GAS CARD |
|
| 12/28/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*FURNACE VENT MUST INCREASE TO 4" AT OUTLET ON FURNACE. CONNECT OVERFLOW SENSOR ON CONDENSATE PUMP CONDENSATE LINE ON ROOF VENT MUST BE DOWNSTREAM OF THE TRAP. REMOVE SCREWS FROM DRYER VENT & EXTEND BEYOND WALL. EXPOSE DRYER VENT FOR INSPECTION. EXTEND WATER HEATER VENT 2' ABOVE UPPER ROOF BOND THE GAS LINE TO THE ELC. SERVICE 15 PSI TEST IS OK CAP OFF GAS VALVE @ DRYER WILL LEAVE GAS CARD ON FINAL INSPECTION |