Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/01/2005 | MECHANICAL - FINAL | Denied | 1) YOU CANNOT STRAP FLEX DUCT WITH PLUMBERS TAPE. MUST BE MINIMUM 1 1/2" WIDE STRAP EVERY 5' 2) THE 2000 IECC REQUIRES ALL SUPPLY DUCTS OUTSIDE OF THE BLDG TO BE INSULATED WITH R8 INSULATION. R4.2 FLEX CAN ONLY BE USED ON THE RETURN AIR DUCT. INSULATE ALL SHEET METAL FITTINGS WITH 2" FOIL WRAP 3) GAS PIPE AND ELECTRIC CONDUIT ARE BLOCKING ACCESS TO SERVICE PANEL ON A/C UNIT 4) LOW VOLTAGE WIRE EXPOSED OUTSIDE THE BLDG MUST BE PROTECTED FROM DRAINAGE-USE CONDUIT |
|
| 11/29/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |