Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/27/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A BUSHING WHERE CONDUCTORS PASS THROUGH DISCONNECT INTO A/C CABINET 2) DO NOT HAVE WIRES FROM SURGE PROTECTOR CONNECTED TO LUGS IN DISCONNECT. ONLY 1 WIRE ALLOWED ON EACH LUG. USE WIRE NUTS IF NECESSARY 3) DO NOT USE WHITE WIRES FOR POWER TO A/C UNIT 4) SUPPORT CONDENSATE DRAIN EVERY 4' & TERMINATE TO WITHIN 6" OF THE GROUND |