Permit: T05ME00856

Parcel: 12603177A


Addresses:

605 N SWAN RD

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/09/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*ALL UNITS
ELECTRICAL-BLOCK, CLAMP, SECURE CONDUIT OUT OF CIRCUIT BKR. PANEL ON SIDE OF WALL UP INTO ATTIC SPACE
PROVIDE CONNECTOR OUT OF SWITCH INTO UNIT
TAPE WHITE WIRES W/BLOCK TAPE
PROVIDE FLASHINGS AT ELECTRICAL GAS LINE PENETRATIONS
DUCT INSULATION. ARE OLD EVAP. GALV. ELLS INSULATED? PROVIDE WRAP AND JACKET OR DUCT LINER, EQUAL TO R.6