Permit: T05ME00847

Parcel: 136241370


Addresses:

6726 E MARY DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/07/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/04/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*VENT CONNECTOR ON FURNACE INSTALLED UPSIDE DOWN. CRIMPED ENDS RUNNING WRONG DIRECTION. PROVIDE A HOSE CLAMP ON CONDENSATE PUMPS
10/28/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*PVC DRAIN PIPE ON THE COIL MUST HAVE CLEARANCE FROM THE SINGLE WALL VENT CONNECTOR.
USE COPPER WITHIN 6" OF VENT. PROVIDE A HOSE CLAMP ON CONDENSATE PUMP.
PROVIDE A PERMIT FOR THE ELECTIRCAL UPGRADE & A PERMIT FOR THE NEW WATER HEATER. PROVIDE A PETITION OF APPEAL FOR THE T & P 4 RELIEF DRAIN. RECALL FOR INSPECTION