Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 01/25/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - #4, STILL NOT FUSED CORRECTLY - PROVIDE AN ELBOW & NIPPLE AT END OF CONDENSATE DRAINS & DIVERT WATER AWAY FROM BLDG. - #109, HEAT STRIP FUSES TOO SMALL - PROVIDE SHEETMETAL COVERS OVER SIDES OF CANVAS CONNECTORS. - #8 ALL FUSES INCORRECT - PROVIDE 30 AMP. FUSES ONLY IN ALL HEAT STRIPS - CHECK ALL A/C FUSES |
|