Permit: T05ME00830

Parcel: 123021960

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/30/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
01/25/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- #4, STILL NOT FUSED CORRECTLY
- PROVIDE AN ELBOW & NIPPLE AT END OF CONDENSATE DRAINS & DIVERT WATER AWAY FROM BLDG.
- #109, HEAT STRIP FUSES TOO SMALL
- PROVIDE SHEETMETAL COVERS OVER SIDES OF CANVAS CONNECTORS.
- #8 ALL FUSES INCORRECT
- PROVIDE 30 AMP. FUSES ONLY IN ALL HEAT STRIPS
- CHECK ALL A/C FUSES
12/06/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
2 TON PKG ROOFTOP HEAT PUMPS
1. I.D UNIT/APT NUMBER ON UNITS ON ROOF.
2. MARK DATA PLATES W/PROPER SIZE AUX. HT. STRIPS.
3. LEAVE ALL UNITS PROPERLY FUSED
50 AMP. MAIN BKR. IN PANEL?
APT. 11 NOT PROPERLY FUSED (EXAMPLE)